Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.3.3.(6) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Sprinkler protection of linen chutes and refuse chutes,
and rooms or bins into which the chutes discharge, in buildings described
in Sentence 1.3.3.2.(1) of Division A. Application 2: This also applies to chutes and shafts in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(7), except where the chute
or shaft is entirely contained within a dwelling unit.
|
Top of Page | |
Intent | Intent 1: To limit the probability that a fire involving a linen chute
or refuse chute, or a room or bin into which the chute discharges, will spread
to other parts of the building, which could lead to harm to persons.
|