Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.4.2.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Separation of a horizontal service space or other concealed space located above a required vertical fire separation from the remainder of the building, where the construction between the horizontal service space or other concealed space, and the space below, is a fire separation with a fire-resistance rating equivalent to that required for the vertical fire separation.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to a horizontal service space that penetrates a required vertical fire separation, as stated in Sentence 3.6.4.2.(1).
Exceptions: 
except:
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentence 3.1.8.3.(1), which would otherwise require the space between a horizontal service space or other concealed space, and a required vertical fire separation, to be divided at the fire separation, if certain conditions are met.
This is to limit the probability that a fire in one fire compartment will spread to another fire compartment by means of the horizontal service space or concealed space, which could lead to harm to persons in the other compartment.