Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.5.2.(2) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Combustible fabric vibration
isolation connectors [in air duct systems], where the connectors:
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to:
|
Top of Page | |
Intent | Intent 1: To exempt combustible fabric vibration isolation connectors
between ducts and air outlet units from the requirements of Sentence 3.6.5.2.(1),
which would otherwise require the connectors to be noncombustible, if certain
conditions are met. This is to limit the probability that
the connectors will contribute to the growth or spread of fire, which could
lead to the spread of fire to other parts of the building by means of the
air duct systems, which could lead to harm to persons.
|