Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.5.4.(5) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Foamed plastic insulation used as part of an air duct
system or for insulating an air duct, in buildings described
in Sentence 1.3.3.2.(1) of Division A. Application 2: This also applies to:
Exceptions:
except as exempted in Sentence 3.6.5.4.(6), which applies
to foamed plastic insulation that is:
|
Top of Page | |
Intent | Intent 1: To limit the probability that foamed plastic insulation
will be used in air duct systems or for insulating air ducts, which could
lead to the insulation contributing to the growth or spread of fire, which
could lead to the spread of fire to other parts of the building by means of
the air duct systems, which could lead to harm to persons. |