Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.5.5.(2) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Maximum flame-spread rating of combustible insulation and coverings on piping in horizontal service spaces or vertical
service spaces. This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to:
Exceptions:
except as exempted in Sentence 3.6.5.5.(5), which applies
to combustible insulation and coverings on piping
in concealed spaces, floor slabs or noncombustible enclosures.
|
Top of Page | |
Intent | Intent 1: To limit the probability that combustible insulation and
coverings on piping located in certain spaces will have inappropriately high
flame-spread properties, which could lead to the spread of fire across the
exposed surfaces of the material, which could lead to the spread of fire to
other parts of the building, which could lead to harm to persons.
|