Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.5.6.(5)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Register boxes installed in floors directly over pipeless furnaces, where the register boxes:
  • are double-walled with not less than 100 mm between walls, or
  • have the warm-air passage completely surrounded by the cold-air passage.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
  • the fire safety characteristics of heating, ventilating and air-conditioning systems, as stated in Article 6.2.1.2., and
  • buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], with respect to:
    • mechanical ventilation systems other than self-contained systems serving single dwelling units, as stated in Sentence 9.32.1.1.(2),
    • the ventilation of storage garages for more than 5 motor vehicles in residential occupancies, as stated in Sentence 9.32.1.1.(3),
    • mechanical ventilation systems used for the ventilation of rooms and spaces in dwelling units during the non-heating season, where natural ventilation is not provided in accordance with Article 9.32.2.2., as stated in Clause 9.32.2.1.(1)(b),
    • heating and air-conditioning systems other than those serving individual dwelling units, as stated in Sentence 9.33.1.1.(2), and
    • air duct distribution systems in which the rated heat input exceeds 120 kW, as stated in Sentence 9.33.6.1.(2).
Top of Page
Intent
Intent 1: 
To exempt register boxes installed in floors directly over pipeless furnaces from the requirements of Sentences 3.6.5.6.(2) to (4), which would otherwise require certain clearances between the register boxes and combustible material, if certain conditions are met.
This is to limit the probability that combustible material will be ignited by the register boxes, which could lead to the spread of fire to other parts of the building, which could lead to harm to persons.