Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.3.2.(2) | Application | Intent |
OP3 |
Objective | OP3 Protection of Adjacent Buildings from Fire |
Attribution | |
Application | Application 1: Calculating the area of an exposing
building face, where the building is divided
into fire compartments by fire
separations having a fire-resistance rating of
not less than 45 min. This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of Sentence 3.2.3.2.(1) and
state a different [less onerous] method for calculating the area of an exposing
building face, if certain conditions are met, on the basis that the conditions
provide an equivalent level of protection. This [the conditions]
is to limit the probability that an entire exposing building face will be
involved in a fire, which could lead to the spread of fire from the subject
building to an adjacent building, which could lead to damage to the adjacent
building.
|