Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.3.9.(1) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Minimum fire-resistance rating of
structural members, including beams, columns and arches, placed wholly or
partly outside an exterior face of a building and
less than 3 m from the property line or centreline of a public
thoroughfare. This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
|
Top of Page | |
Intent | Intent 1: To limit the probability that the structural members in
the subject building will prematurely fail from exposure to a fire outside
of the building during the time required for emergency responders to perform
their duties, which could lead to damage to the subject building.
|