Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.4.18.(9)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Silencing and restoration of audible signal devices [forming part of a fire alarm system] located within dwelling units, in buildings described in Sentence 1.3.3.2.(1) in which fire alarm systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1).
Exceptions: 
except as permitted by Sentence 3.2.4.18.(13), which applies to automatic signal silencing for audible signal devices within dwelling units that are wired on separate signal circuits.
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentence 3.2.4.6.(2) and permit manual silencing switches outside the fire alarm control unit, where silenced audible signal devices automatically restore to normal operation after 10 min.
This is to limit the probability that audible signal devices will:
  • be inadvertently or purposely silenced [made inoperative or damaged] as a result of false alarms, and
  • not be restored to normal operation after being silenced.
This is to limit the probability of the signal devices not operating in a fire situation, which could lead to persons not being promptly notified, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.