Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.18.(10) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Connection of audible signal devices to the fire alarm
system located within dwelling units or suites of residential occupancy.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which fire alarm systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which fire alarm systems are installed, as stated in Sentence 9.10.18.6.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that disconnected (open circuit)
audible signal devices will interfere with the ability of devices in other
specified areas, public corridors or suites to sound an alarm, which could
lead to persons in areas outside the dwelling unit or suite not being promptly
notified of a fire situation, which could lead to delays in the evacuation
or movement of persons to a safe place, which could lead to harm to persons.
|
Top of Page |