Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.4.21.(3) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Provisions in voice communication systems for silencing alert signals and alarm signals in
2 stage fire alarm systems when voice messages are being transmitted.
This applies to voice communication systems required by Sentence 3.2.6.8.(1) in buildings:
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of Sentence 3.2.4.6.(2) and
permit manual [alarm and alert] silencing switches outside the fire alarm
control unit, if silencing can only be done after the alert signal has sounded
initially for not less than a certain period of time. This
[the silencing provision] is to limit the probability that voice messages
will not be heard or understood, which could lead to persons not being instructed
in a fire situation, which could lead to inappropriate action by such persons,
which could lead to delays in evacuation or moving to a safe place, which
could lead to harm to persons.
This [the alert signal sounding for not less than a certain period
of time] is to limit the probability that designated persons [staff] will
be unaware or misinformed of a fire situation, which could lead to:
|