Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.14.(3) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Separation, with respect to the type of construction,
of combustible sprinkler piping from the area
served by the sprinkler system and from any other fire
compartment. This applies to wet systems in residential occupancies or other light hazard occupancies, in buildings described
in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems
are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8).
Exceptions:
except as exempted in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that combustible sprinkler piping
will not be protected against fire exposure, which could lead to the failure
of the piping in a fire situation, which could lead to the fire not being
suppressed or controlled, which could lead to the spread of fire to other
parts of the building, which could lead to harm to persons. |