Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.14.(4) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Maximum distance between the edge of an opening through
a ceiling that is not protected in conformance with Sentence 3.2.5.14.(3) and
the nearest sprinkler head, where combustible sprinkler
piping is located above the ceiling. This applies to
wet systems in residential occupancies or other
light hazard occupancies, in buildings described
in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems
are installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8).
Exceptions:
except as exempted in Sentence 3.2.5.14.(5), which applies
to combustible sprinkler piping that has been
tested in conformance with ULC/ORD-C199P and has been shown to meet the requirements
of that Guide without additional protection.
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of Sentence 3.2.5.14.(3) and
permit openings in ceilings if certain conditions are met. These
[the conditions] are to limit the probability of delay in sprinkler operation
in a fire situation, which could lead to failure of the system, which could
lead to the fire not being suppressed or controlled, which could lead to the
spread of fire to other parts of the building, which could lead to damage
to the building or facility.
Intent 2: To direct Code users to Sentence 3.2.5.14.(3) for requirements
pertaining to the protection of ceiling openings. |
Top of Page |