Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.5.14.(5)
+
Application
Application 1: 
Combustible sprinkler piping, that has been tested in conformance with ULC/ORD-C199P, for wet systems in residential occupancies or other light hazard occupancies.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which automatic sprinkler systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] in which automatic sprinkler systems are installed, as stated in Sentence 9.10.1.2.(8).
Top of Page
Intent
Intent 1: 
To exempt combustible sprinkler piping from the requirement for additional protection as specified in Sentences 3.2.5.14.(3) and (4), where the combustible sprinkler piping has been tested in conformance with ULC/ORD-C199P and has been shown to meet the requirements of that Guide without additional protection.