Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.7.5.(1)
OS1OP1OP3OS3
ObjectiveOP1 Fire Protection of the Building
Attribution
Application
Application 1: 
Installation of emergency electrical power systems, in buildings described in Sentence 1.3.3.2.(1) of Division A, used to supply emergency power to:
  • emergency lighting systems, as required in Articles 3.2.7.3. and 3.2.7.4.,
  • fire alarm systems, as required in Article 3.2.7.8.,
  • voice communication systems in high buildings, as required in Sentence 3.2.7.8.(1),
  • elevators in buildings more than 36 m high, as required in Clause 3.2.7.9.(1)(a),
  • water supply for firefighting, as required in Clause 3.2.7.9.(1)(b), and
  • fans and other electrical equipment that are installed to maintain air quality and venting in high buildings defined in Subsection 3.2.6., as required in Clauses 3.2.7.9.(1)(c) and (d).
Exceptions: 
except as stated in:
  • Article 3.2.7.6., which applies to hospitals and nursing homes, and
  • Article 3.2.7.7., which applies to gas fuel-fired engines or turbines for an emergency electric power supply dependent on a fuel supply from outside the building.
Top of Page
Intent
Intent 1: 
To limit the probability that emergency electrical power systems will not meet proper standards, which could lead to emergency electrical power systems not performing as intended when there is a loss of normal power in a fire situation, which could lead to the inability of the emergency electrical power systems to supply fire protection systems, which could lead to the inability of:
  • sprinkler, standpipe and hose systems, and other fire suppression systems [that rely on booster or fire pumps, or electrical power] to control or suppress a fire, which could lead to the spread of fire, and
  • smoke management systems to control smoke conditions as originally intended, which could lead to the migration of smoke from one floor area or fire compartment to other parts of the building.
This is to limit the probability of damage to the building.