Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.7.6.(1)
OS1OP1OP3OS3
ObjectiveOP1 Fire Protection of the Building
Attribution
Application
Application 1: 
Installation of emergency electrical power supply systems for emergency equipment required by Part 3 for health care facilities.
This applies to emergency electrical power supply systems, for buildings described in Sentence 1.3.3.2.(1) of Division A, used to supply emergency power to:
  • emergency lighting systems, as required by Articles 3.2.7.3. and 3.2.7.4.,
  • fire alarm systems, as required by Article 3.2.7.8.,
  • voice communication systems in high buildings, as required by Sentence 3.2.7.8.(1),
  • elevators in buildings more than 36 m high, as required by Clause 3.2.7.9.(1)(a),
  • water supply for firefighting, as required by Clause 3.2.7.9.(1)(b), and
  • fans and other electrical equipment that are installed to maintain air quality and venting in high buildings defined in Subsection 3.2.6., as required by Clauses 3.2.7.9.(1)(c) and (d).
Exceptions: 
except as stated in Article 3.2.7.7., which applies to gas fuel-fired engines or turbines for an emergency electric power supply dependent on a fuel supply from outside the building.
Top of Page
Intent
Intent 1: 
To limit the probability that emergency electrical power supply systems will not meet proper standards, which could lead to emergency electrical power supply systems not performing in the way intended when there is a loss of normal power in a fire situation, which could lead to the inability of the emergency electrical power supply systems to supply fire protection systems, which could lead to the inability of:
  • sprinkler, standpipe and hose systems, and other fire suppression systems [that rely on booster or fire pumps, or electrical power] to control or suppress a fire, which could lead to the spread of fire, and
  • smoke management systems to control smoke conditions as originally intended, which could lead to the migration of smoke from one floor area or fire compartment to other parts of the building.
This is to limit the probability of damage to the building or facility.