Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.8.2.(1)
+
Application
Application 1: 
Protection of mezzanines, where mezzanines:
  • serve a Group A, C, D, E or F major occupancy,
  • are 500 m2 or less in area, and
  • conform to Sentence 3.2.1.1.(3) or (4).
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], where there are:
  • openings through floors that are not protected by shafts or closures, as stated in Sentence 9.10.1.2.(6), or
  • interconnected floor spaces, as stated in Sentence 9.10.9.5.(1).
Top of Page
Intent
Intent 1: 
To exempt mezzanines serving certain major occupancies from the requirements of Sentence 3.2.8.1.(1) and Articles 3.2.8.3. to 3.2.8.9., which would otherwise require a vertical fire separation or certain fire protection measures, on the basis that the mezzanine area is limited in size and sufficiently open to allow occupants to detect a threat to their safety and not be excessively delayed in reaching an exit.