Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.3.5.(9)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Separation of patients' sleeping rooms from the remainder of the floor area in hospitals or nursing homes.
This applies to care or detention occupancy in buildings described in Sentence 1.3.3.2.(1) of Division A.
Exceptions: 
except as exempted in:
  • Sentence 3.3.3.5.(10), which applies to a group of intercommunicating patients' rooms, and
  • Sentence 3.3.3.5.(11), which applies to roller latches on doors.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To limit the probability that smoke will spread from a patient's sleeping room to the remainder of the floor area, which could lead to harm to persons.
Intent 2: 
To limit the probability that smoke will spread from a patient's sleeping room to the remainder of the floor area, which could lead to fire emergency response operations being delayed or ineffective, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.