Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.3.5.(11)
+
Application
Application 1: 
Roller latches on doors in fire separations required by Sentence 3.3.3.5.(9) to separate patients' sleeping rooms from the remainder of the floor area in hospitals or nursing homes.
This applies to care or detention occupancy in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentences 3.1.8.13.(1) and 3.3.3.5.(9), which would otherwise require positive latching devices, and permit roller latches on the basis that doors would be propped open to overcome the inconvenience of patient care staff having to use door release hardware to move into or out of a room, frequently while carrying supplies, thereby defeating the door's role in smoke control and compromising the safety of persons in the fire compartment.