Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.2.5.(1)
OS3
ObjectiveOS3 Safety in Use
Attribution
Application
Application 1: 
Location of exits with respect to limiting the maximum travel distance to at least one exit, where more than one exit is required from a floor area.
This applies to floor areas that are intended for occupancies, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
  • travel distances within a room or suite to the nearest egress doorway, as stated in Sentence 3.3.1.6.(1),
  • travel distances from a zone in a floor area that is not sprinklered and that has a barrier-free path of travel, as stated in Subclause 3.3.1.7.(1)(b)(ii),
  • tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1), and
  • travel distances in public corridors referred to in Clause 3.4.2.5.(1)(d), in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.9.8.1.(3).
Exceptions: 
except as stated in:
  • Sentence 3.1.6.2.(1), which prohibits air-supported structures to be located above the first storey on any building,
  • Sentence 3.1.6.2.(2), which prohibits air-supported structures to be used for classrooms or for Groups B, C, or Group F, Division 1 major occupancies,
  • Sentence 3.1.6.2.(3), which requires air-supported structures to be designed as open floor spaces without interior walls, mezzanines, intermediate floors or similar construction,
  • Sentence 3.3.1.3.(5), which applies to rooftop enclosures,
  • Sentence 3.3.2.5.(6), which applies to assembly occupancies,
  • Sentence 3.4.2.2.(2), which applies to mezzanines that:
    • are not required to terminate at a vertical fire separation [see Article 3.2.8.1.],
    • are not intended for an occupant load more than 60,
    • do not exceed the area limits for rooms and suites in Table 3.4.2.2., and
    • have limited travel distances to egress doors or stairs,
  • Sentence 3.4.2.2.(3), which applies to at least half of the required means of egress from a mezzanine if the mezzanine is not required to terminate at a fire separation as permitted by Sentence 3.2.8.2.(1), and
  • Sentence 3.4.2.5.(2), which applies when exits are placed along the perimeter of the floor area and are not more than 60 m apart.
Top of Page
Intent
Intent 1: 
To limit the probability of excessive travel distances to an exit in an emergency situation, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.