Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.2.1.(7) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Minimum fire-resistance rating of fire separations separating service
rooms from the remainder of the building,
where the service room is located in a floor
area that is not sprinklered throughout.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Exceptions:
except as exempted in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that fire will spread from a service
room that is in a storey not sprinklered throughout and that contains equipment
not otherwise covered by Sentences 3.6.2.1.(1) to (6) to other parts of the building,
which could lead to damage to the building. Intent 2: To limit the probability that a fire originating in a location
outside a service room will spread into the service room, which could lead
to the disruption and discontinuation of service from equipment located in
the service room, which could lead to an undue fire hazard in the building,
which could lead to damage to the building. |