Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.2.1.(8)
+
Application
Application 1: 
Fire separations required by Sentences 3.6.2.1.(1) and (7) for a service room, where:
  • the room contains a limited quantity of service equipment, and
  • the service equipment does not constitute a fire hazard.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Exceptions: 
except as exempted in:
  • Sentence 3.6.2.1.(1), which applies to service rooms that contain fuel-fired appliances,
  • Sentence 3.6.2.1.(3), which applies to service rooms that contain solid-fuel-fired appliances,
  • Sentence 3.6.2.1.(4), which applies to service rooms that contain incinerators,
  • Sentence 3.6.2.1.(5), which applies to service rooms intended to contain equipment that uses a liquid having a flash point below 93.3°C,
  • Sentence 3.6.2.1.(6), which applies to service rooms that contain electrical equipment that is required to be located in a service room by CSA C22.1, “Canadian Electrical Code, Part I,”
  • Sentence 3.6.2.1.(7), which applies when the service room is located in a storey that is not sprinklered throughout,
  • Sentence 3.6.2.1.(8), which applies when the service room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard,
  • Article 3.6.2.5., which applies to rooms for the storage of combustible refuse, and
  • Article 3.6.2.7., which applies to electrical equipment vaults required by provincial, territorial, or municipal regulations, or CSA C22.1, “Canadian Electrical Code, Part I,” in the absence of such regulations.
Top of Page
Intent
Intent 1: 
To exempt a service room containing equipment that does not constitute a fire hazard from the requirements of Sentences 3.6.2.1.(1) and (7), which would otherwise require the service room to be separated from the remainder of the building by a fire separation, on the basis that the risk of fire originating and spreading from the service room is minimized.