Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.6.2.7.(5) | Application | Intent |
+ |
Application | Application 1: Explosion-relief devices, vents or other protective
measures for electrical equipment vaults that contain dielectric-liquid-filled
electrical equipment, in buildings described in Sentence 1.3.3.2.(1). This applies to electrical equipment
vaults [referred to in Sentence 3.6.2.7.(1)] required by:
Application 2: This also applies to transformer vaults in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(1). |
Top of Page | |
Intent | Intent 1: To expand the application of Sentence 3.3.1.20.(2),
which would otherwise apply only to spaces in which substances or conditions
that have the potential to create an explosion hazard are present as a result
of the principal use of a building, and make it applicable to an electrical
equipment vault that contains dielectric-liquid-filled electrical equipment
on the basis that this equipment poses a risk of explosion. |