Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.2.3.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum distance between 2 required exits from floor areas that are intended for occupancies, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to:
  • the minimum distance between stairs serving a roof intended for an occupant load more than 60, as stated in Sentence 3.3.1.3.(4), and
  • tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
  • Sentence 3.1.6.2.(1), which prohibits air-supported structures to be located above the first storey on any building,
  • Sentence 3.1.6.2.(2), which prohibits air-supported structures to be used for classrooms or for Groups B, C, or Group F, Division 1 major occupancies,
  • Sentence 3.1.6.2.(3), which requires air-supported structures to be designed as open floor spaces without interior walls, mezzanines, intermediate floors or similar construction,
  • Sentence 3.3.1.3.(5), which applies to rooftop enclosures,
  • Sentence 3.4.2.3.(2), which applies to measurement, for the purpose of applying Clauses 3.4.2.3.(1)(a) and (b), of the minimum distance between 2 required exits from a floor area that is intended for occupancy,
  • Sentence 3.4.2.2.(2), which applies to mezzanines that:
    • are not required to terminate at a vertical fire separation [see Article 3.2.8.1.],
    • are not intended for an occupant load more than 60,
    • do not exceed the area limits for rooms and suites in Table 3.4.2.2., and
    • have limited travel distances to egress doors or stairs, and
  • Sentence 3.4.2.2.(3), which applies to at least half of the required means of egress from a mezzanine if the mezzanine is not required to terminate at a fire separation as permitted by Sentence 3.2.8.2.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that exits will be located too close to one another, which could lead to persons not having a choice of an alternative egress route in the event that one route to the exits is blocked or obstructed in a fire situation, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.