Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
6.3.1.2.(2) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Design and installation of masonry
or concrete chimneys, in buildings described
in Sentence 1.3.3.2.(1) of Division A. Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], with respect to heating systems, other than those serving individual dwelling units, as stated in Sentence 9.33.1.1.(2).
Exceptions:
except as stated in Sentence 6.3.1.2.(1), which applies to
rectangular masonry or concrete chimneys not
more than 12 m in height that serve:
|
Top of Page | |
Intent | Intent 1: To limit the probability that the performance of chimneys
will fall significantly below expectations, which could lead to radiant heat
loss, which could lead to failure, which could lead to the ignition of combustible
building elements, which could lead to harm to persons. |