Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.9.4.2.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Fire-resistance rating required in Sentence 9.9.4.2.(1) [minimum fire-resistance rating of fire separations that separate exits from adjacent floor areas and from other exits ], where there is no floor assembly above the floor area, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except:
  • for exterior doorways,
  • for exits that serve not more than one dwelling unit, as stated in Sentence 9.9.4.1.(1),
  • as stated in Sentence 9.9.4.2.(5), which applies to exterior exit passageways,
  • as stated in Sentence 9.9.4.4.(1), which applies to openings near unenclosed exit stairs and ramps,
  • as stated in Sentence 9.9.4.7.(1), which applies to stairways in 2-storey Group D or E buildings, and
  • as stated in Article 9.9.8.5., which applies to exits through lobbies.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread into an exit, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.
Intent 2: 
To limit the probability that fire will spread from one floor area to another floor area by means of an exit, which could lead to harm to persons in the other floor area.