Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.9.4.2.(5)
+
Application
Application 1: 
Exterior exit passageways, where the passageways:
  • have not less than 50% of their exterior sides open to the outdoors, and
  • are served by an exit stair at each end.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except:
  • for exits that serve not more than one dwelling unit, as stated in Sentence 9.9.4.1.(1), and
  • as stated in Sentence 9.9.4.4.(1), which applies to openings near unenclosed exit stairs and ramps.
Top of Page
Intent
Intent 1: 
To exempt some configurations of exterior exit passageways from the application of Sentence 9.9.4.2.(1), which would otherwise require the passageway to be separated from floor areas, on the basis that it is not expected that smoke will accumulate in the passageway and exits are available at each end of the passageway.