Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.9.5.3.(1)
OS3
ObjectiveOS3 Safety in Use
Attribution
Application
Application 1: 
Maximum horizontal projection of obstructions located within 1 980 mm of floors of exit passageways, corridors used by the public or public corridors, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except:
  • for means of egress that are within dwelling units or that serve not more than one dwelling unit, as stated in Sentence 9.9.5.1.(1),
  • as stated in Sentence 9.9.5.3.(2), which applies when the obstruction extends to less than 680 mm above the floor, and
  • as stated in Sentence 3.8.1.3.(1), which applies to barrier-free design in buildings described in Sentence 3.8.1.1.(1) [see Sentence 9.5.2.1.(1)].
Top of Page
Intent
Intent 1: 
To limit the probability that a person with a visual disability will hit an obstruction in a corridor that cannot be detected by a cane, which could lead to harm to persons.