Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.9.8.1.(1)
+
Application
Application 1: 
Meaning of travel distance for the purposes of Subsection 9.9.8., in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to certain mezzanines, as stated in Sentence 9.9.8.6.(1).
Exceptions: 
except as stated in:
  • Sentence 9.9.8.1.(2), which applies to rooms or suites that are separated from the remainder of the floor area they serve by fire separations that have a fire-resistance rating of at least 45 min or, in sprinklered buildings, by fire separations that are not required to have a fire-resistance rating, and
  • Sentence 9.9.8.1.(3), which applies to public corridors that conform to Subclauses 3.4.2.5.(1)(d)(i) to (d)(iv), where
    • the ceiling height is not less than 4 m above all floor surfaces
    • the building is sprinklered throughout, and
    • not more than one half of the required egress doorways from a room or suite open into the public corridor if the room or suite is required to have more than one egress doorway.
Top of Page
Intent
Intent 1: 
To define how to measure travel distance within a floor area for the location of exits or for the purposes of Subsection 9.9.8.