Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.9.11.3.(3) | Application | Intent |
OS3 |
Objective | OS3 Safety in Use |
Attribution | |
Application | Application 1: Actuation and minimum duration of operation of the
lighting required in Sentence (1) [emergency lighting
in exits, principal routes providing access
to exits in open floor areas, corridors
used by the public, underground walkways, and public corridors ], when the [normal] electric lighting
in the affected area is interrupted, in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9]. Application 2: This also applies to the illumination of exit signs,
as stated in Sentence 9.9.10.7.(1).
Exceptions:
except for exits that serve only one dwelling unit, as stated in Sentence 9.9.11.1.(1).
|
Top of Page | |
Intent | Intent 1: To limit the probability that certain areas in buildings
will have inadequate illumination when there is a loss of normal power, which
could lead to safety hazards [bumping, tripping, falling, etc.], which could
lead to harm to persons. Intent 2: To limit the probability that certain areas in buildings
will have inadequate illumination when there is a loss of normal power in
an emergency situation, which could lead to delays in the evacuation or movement
of persons to a safe place, which could lead to harm to persons.
|
Top of Page |