Warning This information has been archived because it is outdated and no longer relevant.

Archived Content

Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.1.1.(1)
+
Application
Application 1: 
Roofs that are:
  • pitched at an angle of 60°, or more to the horizontal, and
  • adjacent to a space intended for occupancy within a building.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To state the conditions under which roof assemblies must be considered as exterior walls for the purposes of the application of Section 9.10.
This is based on the potential radiation hazard of nearly-vertical roofs which, under fire conditions, could radiate sufficient heat to ignite nearly-parallel surfaces of adjacent buildings.
Top of Page