Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.1.2.(5)
OS1+
ObjectiveOS1 Fire Safety
Attribution
[F01-OS1.1] Applies to portion of Code text: “ ... facilities for the dispensing of fuel shall not be installed in any building.”
Application
Application 1: 
Facilities for the dispensing of fuel, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Sentence 3.3.5.8.(2), which permits canopies that are open on not less than 75% of their perimeter to be used for the dispensing of fuel having a flash point below 37.8°C.
Top of Page
Intent
Intent 1: 
To limit the probability that vapours will migrate into other areas of a building, which could lead to the accumulation of the vapours in sufficient quantity to form an ignitable mixture, which could lead to the ignition of the vapours from a nearby ignition source, which could lead to harm to persons.
Intent 2: 
To limit the probability that vapours will accumulate in sufficient quantity to form an ignitable mixture, which could lead to the ignition of the vapours from a nearby ignition source, which could lead to harm to persons.