Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.5.1.(3)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Offsetting of boxes referred to in Sentence 9.10.5.1.(2) [electrical and similar service outlet boxes], where such boxes are located on both sides of walls required to provide a fire-resistance rating [and that also form a fire separation].
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To limit the probability that certain service equipment penetrating wall assemblies that also form a fire separation will contribute to the spread of fire through the assemblies, which could lead to a loss of integrity of the fire separation, which could lead to the spread of fire and smoke from one fire compartment to another, which could lead to harm to persons in the other compartment.