Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.9.4.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Floor assemblies as fire separations, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in:
  • Sentences 9.10.9.1.(1) and 9.10.9.4.(2), which apply to floor assemblies that are contained within dwelling units,
  • Sentence 9.10.9.4.(3), which applies to
    • floor assemblies for which no fire-resistance rating is required by Subsection 9.10.8., and
    • floors of mezzanines not required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2., and
  • Sentence 9.10.9.4.(4), which applies to floors above crawl spaces that are not required by Article 9.10.8.9. to be constructed as basements.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from a lower storey of a building to an upper storey during the time required to achieve occupant safety and for emergency responders to perform their duties, which could lead to harm to persons in the upper storey.