Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.9.6.(5) | Application | Intent |
+ |
Application | Application 1: Combustible totally enclosed
raceways that are embedded in concrete floor slabs, in an assembly required
to have a fire-resistance rating, where the
concrete provides not less than 50 mm of cover between the raceway
and the bottom of the slab. This applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9].
|
Top of Page | |
Intent | Intent 1: To exempt combustible totally enclosed raceways from the
requirements of Sentence 9.10.9.6.(2) if certain conditions are met,
on the basis that the raceways are protected by a concrete covering and should
not contribute significantly to the growth and spread of fire.
|
Top of Page |