Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.9.7.(1) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Combustible piping used
in any part of a drain, waste and vent piping system, where any part of that
system partly or wholly penetrates:
This applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9].
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To limit the probability that combustible piping penetrating
rated assemblies will contribute to the growth and spread of fire within the
assemblies, which could lead to the structural failure and collapse of the
assemblies, which could lead to damage to the building. Intent 2: To limit the probability that combustible piping penetrating
rated fire separations will contribute to the growth and spread of fire within
the fire separations, which could lead to a loss of integrity of the fire
separations, which could lead to the spread of fire and smoke from one fire
compartment to another, which could lead to damage to the building.
|
Top of Page |