Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.9.7.(4)
+
Application
Application 1: 
Combustible drain piping penetrating a horizontal fire separation or a membrane that contributes to the required fire-resistance rating of a horizontal fire separation, where the piping leads directly from a noncombustible water closet through a concrete floor slab.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to combustible piping for central vacuum systems, as stated in Sentence 9.10.9.6.(9).
Top of Page
Intent
Intent 1: 
To exempt combustible drain piping from the requirements of Sentence 9.10.9.7.(1) if certain conditions are met, on the basis that the imposed conditions limit the probability of the spread of fire and smoke.