Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.9.10.(2) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Division by fire separations of horizontal service spaces or other concealed spaces
located above required vertical fire separations,
where the construction between such spaces and the spaces below is constructed
as a fire separation having a fire-resistance
rating not less than that required for the vertical fire
separation. This applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9].
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To supersede the requirements of Sentence 9.10.9.10.(1),
which would otherwise require the space between a horizontal service space
or other concealed space and a required vertical fire separation to be divided
at the fire separation, if certain conditions are met. This
is to limit the probability that fire will spread from one fire compartment
to another by means of the horizontal service space or concealed space, which
could lead to harm to persons in the other compartment.
|