Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.9.11.(3)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum fire-resistance rating of fire separations that separate mercantile occupancies from dwelling units, where not more than 2 dwelling units are located in a building containing a mercantile occupancy.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To supersede the requirements of Sentence 9.10.9.11.(2) for a residential occupancy with not more than 2 dwelling units that is adjacent to a mercantile occupancy and permit a reduction in the minimum required fire-resistance rating of the fire separation, on the basis that the number of dwelling units is limited and thus the mercantile occupancy does not pose a risk to a large number of persons.
This is to limit the probability that fire will spread from one mercantile occupancy to an adjacent residential occupancy having a different degree of fire risk, which could lead to harm to persons.