Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.9.15.(2) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Fire-resistance rating of fire separations that separate public
corridors from the remainder of buildings,
where:
This applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9].
Exceptions:
except for residential occupancies.
|
Top of Page | |
Intent | Intent 1: To exempt public corridor separations from the application
of Sentence 9.10.9.15.(1) by waiving the requirement for a minimum 45
min fire-resistance rating if certain conditions are met [i.e. the
floor area is sprinklered throughout and the sprinkler system meets certain
operational requirements]. This is to limit the probability
that a fire will not be controlled or suppressed, which could lead to:
This is to limit the probability of harm to persons.
|