Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.10.4.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Location of fuel-fired appliances and minimum fire-resistance rating of fire separations that separate service rooms containing fuel-fired appliances from the remainder of the building. This applies tobuildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except:
Top of Page
Intent
Intent 1: 
To limit the probability that fire involving a fuel-fired appliance in a service room will spread from the service room to other parts of the building, which could lead to harm to persons.
Intent 2: 
To limit the probability that a fire originating in a location outside a service room will spread into the service room, which could lead to the disruption and discontinuation of service from equipment located in the service room, which could lead to an undue fire hazard in the building, which could lead to harm to persons.
Intent 3: 
To supersede the requirements of Sentence 9.10.10.3.(1).