Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.12.1.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Vertical fire separation of portions of floor areas or mezzanines that do not terminate at an exterior wall, a firewall or a vertical shaft, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in:
  • Sentence 9.10.1.2.(6), which applies to openings through floors that are not protected by shafts or closures,
  • Sentence 9.10.9.5.(1), which applies to interconnected floor spaces, and
  • Sentence 9.10.12.1.(2), which applies to mezzanines that are not required to be considered as storeys by Articles 9.10.4.1. and 9.10.4.2.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from:
  • a lower floor level to upper floor levels, or
  • a floor area into exit stairs.
This is to limit the probability of:
  • delays or ineffectiveness in fire suppression operations, which could lead to the spread of fire, and
  • delays in the evacuation or movement of persons to a safe place.
This is to limit the probability of harm to persons.