Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.12.3.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum horizontal distance between an opening in one exterior wall and an opening in another exterior wall, where:
  • the exterior walls of the building meet at an external angle of 135°, or less, and
  • the openings are in different fire compartments.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Sentence 9.9.4.5.(1), which applies to openings in exterior walls of exits.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from one fire compartment to an adjacent fire compartment through unprotected openings in the exterior wall of the fire compartment of origin, which could lead to harm to persons in the adjacent fire compartment.