Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.13.13.(4)
+
Application
Application 1: 
Fire dampers in noncombustible ducts that pierce fire separations that separate vertical service spaces from the remainder of the building, where:
  • the ducts have a melting point above 760°C, and
  • each individual duct exhausts directly to the outside at the top of the vertical service space.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To exempt certain ducts from the requirements of Sentence 9.10.13.13.(1), which would otherwise require fire dampers to be installed, on the basis that:
  • the ducts are capable of withstanding high temperatures,
  • it is unlikely that hot gases will contact combustible building components, and
  • the lack of dampers in this case will not contribute significantly to the spread of fire.