Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.17.3.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Maximum surface flame-spread rating on at least 90% of the exposed surface of walls in exits.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Sentence 9.10.17.3.(2), which applies to lobbies used as exits.
Top of Page
Intent
Intent 1: 
To exempt certain walls from the requirements of Sentence 9.10.17.1.(1), which would otherwise limit surface flame-spread rating to 150, and require a lower maximum flame-spread rating on at least 90% of the exposed wall surface, on the basis that the lower flame-spread rating is needed in exits to protect persons during evacuation.
Intent 2: 
To limit the probability that certain finishes having an inappropriately high flame-spread property will be used in exits, which could lead to the spread of fire across the exposed surfaces of the finishes, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.