Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.18.3.(2) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Heat detectors or smoke detectors in storage rooms, service
rooms, elevator shafts, chutes, janitors' closets and any other rooms
where hazardous substances are intended to be used or stored.
This applies to buildings to which Part
9 applies [see Sentence 1.3.3.3.(1) of Division A for application of
Part 9] where fire alarm systems are required [see Article 9.10.18.2.].
Exceptions:
except as stated in Sentence 9.10.18.3.(3), which applies to dwelling units and sprinklered buildings.
|
Top of Page | |
Intent | Intent 1: To limit the probability that fire will not be detected
in certain spaces, which could lead to persons not being promptly notified
of a fire situation, which could lead to delays in the evacuation or movement
of persons to a safe place, which could lead to harm to persons.
|