Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.18.4.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Design, with respect to preventing the circulation of smoke, of a recirculating air handling system, where the air handling system:
  • supplies more than one suite on the same floor, or
  • serves more than 1 storey.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] where fire alarm systems are required [see Article 9.10.18.2.].
Exceptions: 
except for recirculating air systems serving not more than one dwelling unit.
Top of Page
Intent
Intent 1: 
To limit the probability that smoke will spread between storeys or suites by means of an air handling system, which could lead to harm to persons.
Intent 2: 
To limit the probability that smoke originating from a fire in an air handling system will spread through the duct system, which could lead to harm to persons.