Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.20.2.(2)
OS1OP1+
ObjectiveOS1 Fire Safety
Attribution
[F12-OS1.2,OS1.5] Applies to portion of Code text: " Access required in Sentence (1) ... provides an opening not less than 1 100 mm high and 550 mm wide, the sill height of which shall not be more than 900 mm above the floor."
Application
Application 1: 
Minimum opening size, and maximum sill height above floor level, of the access [for firefighting] required in Sentence 9.10.20.2.(1) [direct access to the outdoors to at least one street from unsprinklered basements exceeding 25 m in length or width].
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To limit the probability of delays or ineffectiveness in fire emergency response operations, which could lead to:
  • delays in the evacuation or movement of persons to a safe place, and
  • the spread of fire to other parts of the building.
This is to limit the probability of harm to persons.