Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.22.3.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum fire resistance of material protecting combustible wall framing, finishes or cabinets that are:
  • within 450 mm [measured horizontally] of the area where a gas or electric range is to be located, and
  • above the level of the heating elements or burners.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in:
  • Sentence 9.10.22.3.(2), which applies to countertop splash boards or back plates that extend above the level of heating elements or burners, and
  • Sentence 9.10.22.3.(3), which applies to cabinetry located not less than 450 mm above the level of the heating elements or burners.
Top of Page
Intent
Intent 1: 
To limit the probability that heat radiating from a range or from open fire will ignite nearby framing, finishes or cabinetry, which could lead to the spread of fire, which could lead to harm to persons.
Intent 2: 
To supersede the requirements stated in CSA B149.1, referred to in Sentence 9.10.22.1.(1), with regard to natural gas ranges, in cases of conflict.