Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.20.8.4.(4) | Application | Intent |
OH1 | OS2 | OP2 | OS1 | OH4 | OS3 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: In buildings to which Part
9 applies [see Sentence 1.3.3.3.(1) of Division A for application of
Part 9], minimum width and depth of concrete pilasters that support beams
and columns in:
Exceptions:
except as stated in Sentence 9.20.1.1.(2), which applies to buildings other than described above, or where the masonry
is designed for specified loads on the basis of ultimate and serviceability
limit states.
|
Top of Page | |
Intent | Intent 1: To limit the probability that pilasters will be unable to
resist the loads imposed by beams or columns, which could lead to structural
failure of concrete pilasters and cracking of masonry walls. Where
masonry construction is required to provide fire resistance, this is to limit
the probability of compromised fire resistance of the assembly, which could
lead to harm to persons.
|